Detonation-fired pipe flame arrester use, detonation-fired pipe flame arrester model size

Detonation-fired pipe flame arresters are safety devices used to prevent the flame from flammable gases and flammable liquid vapors from spreading outward. When designing the fire retardant inner part, the regular packing is designed according to the medium of different mixed gases, the composition of the gas, the pressure drop, the aspect ratio, and the number of elbows to design the MESG value and reach a certain flame retarding speed value.
China Hardware Business Network

Detonation-fired pipe flame arrester Model: GZW-1

Detonation-fired pipe flame arresters are safety devices used to prevent the flame from flammable gases and flammable liquid vapors from spreading outward. When designing the fire retardant, it is based on the medium and gas of different mixed gases.

The fractional, pressure drop, aspect ratio, and number of elbows are used to design the MESG value and achieve a certain rate of fire resistance. When the flame enters the flame arrester, it is cut into many small pieces by regular flame arresting elements.

The flame flow, due to the heat transfer effect and the wall effect, the incoming gas is cooled, so that the cooled gas does not reach the ignition temperature, and the combustion cannot be formed without the ignition temperature, and finally the flame flow is extinguished.

Thereby achieving the purpose of fire prevention.

caliber:

DN20-500

pressure:

1.6MPa-6.4Mpa

Operating temperature:

-20°C- +480°C

Body material:

Cast steel, stainless steel " target=_blank> stainless steel A3 304 304L 316 316L

Fire retardant material:

Stainless steel " target=_blank> stainless steel 304 304L 316 316L

Sealing Gasket:

NBR rubber PTFE metal Gasket

Manufacturing Standards

GB5908-86 SY7511-87

Explosion-proof grade:

BS 5501: IIA IIB IIC

Connection method:

Flange connection

Detonation-fired pipeline flame arrester use:

1. Torch system.

2. Oil and gas recovery system.

3. Gas analysis system.

4. Gas purification and communication system.

5. Coal mine gas emission system.

6. Heating the furnace fuel gas on the pipe network.

7. Pipes that transport flammable gases.

Detonation-fired pipe flame arrester size:

specification

size

pressure

grade

Dimensions (mm)

Nd

L

H

D

K

DN15













1.6MPa

















125

142

95

65

4*14

DN20

125

142

105

75

4*14

DN25

130

155

115

85

4*14

DN32

150

168

135

100

4*18

DN40

170

180

150

110

4*18

DN50

190

200

165

125

4*18

DN65

205

210

180

145

8*18

DN80

220

220

200

160

8*18

DN100

240

240

220

180

8*18

DN125

280

260

245

210

8*18

DN150

330

285

285

240

8*22

DN200

380

325

340

295

12*22

DN250

450

365

405

335

12*26

DN300

520

400

460

410

12*26

DN350

595

420

520

470

16*26

DN400

645

450

580

525

16*30

DN450

710

480

640

585

20*30

DN500

780

520

715

650

20*33

DN600

895

550

840

770

20*36

The installation and maintenance of the detonation-fired pipeline flame arrester are as follows:

1. Pipeline flame arrester should pay attention to rain, moisture and oil in the process of transportation and storage.

2. The pipe or accessory Flange Gasket connected to the pipe flame arrester shall be annealed and softened aluminum, copper or copper wire.

3. In order to prevent fire, before and after the oxygen pipeline flame arrester with working pressure greater than 0.6MPa, a copper-based alloy (or stainless steel "target=_blank> stainless steel) pipe should be connected, the length is not less than 5 pipe diameter, and not less than 1.5m. ,

It is not allowed to install all fittings.

4. After the pipeline flame arrester is installed on the pipeline, the system strength and leakage test shall be carried out according to the system design rules, and special cleaning shall be carried out.

5. After the pipeline flame arrester is deactivated for a long time, it should be thoroughly cleaned again when it is used again.

Shanghai Nanshi is a professional manufacturer of anti-explosion-fired pipeline flame arresters. The company produces products: breathing valve, flame arrester, fire retardant breathable cap, fireproof vacuum pressure cap, aluminum alloy Ball Valve , aluminum alloy single Flange Ball Valve, unloading oil. Port, double door bottom valve, oil hole and other series of accessories.
You are welcome to visit our website [http://]. If you have any questions, you can call us and we will do our best to provide you with quality service. phone. Http://news.chinawj.com.cn Detonation-fired pipe flame arrester use, detonation-fired pipe flame arrester model size Editor: (Hardware Business Network Information Center) http://news.chinawj.com.cn Detonation-fired pipe flame arrester use, detonation-fired pipe flame arrester model size

Flow Calibration Column is widely used in the flow calibration of metering pump and dosing device, which can accurately calibrate the output flow of metering pump. Major Material: Plexiglass, transparent PVC and stainless steel; Connection methods have internal thread, external thread, flange.

Flow Calibration Column

UPVC Flow Calibration Column,PVDF Flow Calibration Column,Plastic Flow Calibration Column,Transparent Flow Calibration Column

Ningbo Reamac Imp&Exp Co.,Ltd , https://www.rmiplast.com